- 180 -
[
X
LED Monitor Display on the Outdoor Unit Board ]
*1. Output frequency of the inverter depends on the type of compressor and equals the integer multiples (X1, X2 etc.) of the
operating frequency of the compressor.
No
SW
Item
Display
Remarks
1234567890
LD1
LD2
LD3
LD4
LD5
LD6
LD7
LD8
78
0111001000
× Qj
0000 to 9999
79
1111001000
× Qjc
0000 to 9999
80
0000101000
× Qjh
0000 to 9999
81
1000101000
Target Tc
-99.9 to 999.9
The unit is
[°C]
82
0100101000
Target Te
-99.9 to 999.9
83
1100101000
Tc
-99.9 to 999.9
84
0010101000
Te
-99.9 to 999.9
85
1010101000
86
0110101000
87
1110101000
All tempo-
rary frequen-
cies
0000 to 9999
Control data
[ Hz ]
88
0001101000
Control fre-
quency of
COMP 1
0000 to 9999
89
0001101000
Control fre-
quency of
COMP 2
0000 to 9999
90
0101101000
91
1101101000
Operation
frequency of
COMP 1
0000 to 9999
Operation fre-
quency of com-
pressor
[ Hz ]
*1
92
0011101000
93
1011101000
94
0111101000
AK1
0000 to 9999
Control data
95
1111101000
96
0000011000
97
1000011000
FAN1
0000 to 9999
Fan inverter out-
put [ % ]
98
0100011000
99
1100011000
100
0010011000
Number of
fans in oper-
ation
0000 to 9999
101
1010011000
102
0110011000
103
1110011000
104
0001011000
LEV1
0 to 480
Outdoor LEV
opening
(Fully open:
480)
105
1001011000
106
0101011000
107
1101011000
Current data
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...