- 94 -
[
VII
Control ]
2. Operations in each mode
(1) Cooling operation
*Note 1. The indoor fan operates in the cooling mode regardless of the ON/OFF state of the thermostat.
*Note 2. The following two methods are available to perform the test run.
1) Using DipSW3-1 and 3-2 on the outdoor unit
2) Using MA remote controller
Cooling operation
Test run mode
ON
Thermostat ON
3-minute restart
prevention
*Note 1
*Note 2
YES
YES
YES
NO
NO
NO
4-way valve OFF
1. Inverter frequency control
2. Indoor unit LEV, LEV1
control
3. Solenoid valve control
4. Outdoor unit fan control
5. 52C control
Normal operation
During test run mode
Unit in the stopped state
Indoor unit fan
operation
1. Inverter output 0Hz
2. Indoor unit LEV,
LEV1 rated opening
3. All solenoid valves OFF
4. Outdoor unit fan stop
5. 52C OFF