- 161 -
[
IX
Troubleshooting ]
(4) Simple checking procedure for individual components of main inverter circuit
* Before checking, turn the power off and remove the parts to be checked from the control box.
Part name
Judgment method
Diode stack
Refer to "Diode stack" ( 9.[4] -6- (6) )
IPM (Intelligent power
module)
Refer to "Intelligent power module (IPM)" ( 9.[4] -6- (5) )
Rush current protec-
tion resistor
R11, R12
Measure the resistance between terminals: 47 ohm 10%
Electromagnetic con-
tactor
52C(1), 52C2, 52F
DC reactor DCL
Measure the resistance between terminals: 1 ohm or lower (almost 0 ohm)
Measure the resistance between terminals and the chassis:
Current sensor ACCT
Disconnect the CNCT2 connector and measure the resistance between terminals: 280 ohm
30 ohm
1 - 2 PIN (U-phase),3 - 4 PIN (W-phase)
Check point
Judgment value
A1-A2
0.1 k ~ 2.0 k
Button
on
(hold down)
Button
OFF
L1 - T1
L2 - T2
L3 - T3
13 - 14
31 - 32
L1 - T1
L2 - T2
L3 - T3
13 - 14
31 - 32
13
Pushbutton
L1
L3
L2
A1
A2
31
14
T1
T3
T2
32
[In the case of 52C1, 52C2]
13
Pushbutton
L1
L3
L2
A1
A2
14
T1
T3
T2
[In the case of 52F]
1 or less (almost 0 )
1 or less (almost 0 )
1 or less (almost 0 )
1 or less (almost 0 )
1 or less (almost 0 )
U
U
V
IPM
* Check the ACCT connection phase and the
direction of the connection.
W
ACCT-W
W
ACCT-U
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...