[1] Functions and Factory Settings of the Dipswitches
1. Outdoor unit
(1) Main board
Switch
Function
Function according to switch setting
Switch setting timing
OFF
ON
OFF
ON
SWU
1-2
Unit address setting
Set to 00 or 51-100 with the dial switch Before power on
SW1
1-10
For self-diagnosis/op-
eration monitoring
Refer to the LED monitor display on
the outdoor unit board.
Anytime after power on
SW2
1
-
-
-
-
2
Deletion of connec-
tion information
Normal control
Deletion
Before power on
3
Deletion of error his-
tory SW
Storage of IC/OC
error history
Deletion of IC/OC
error history
Anytime after power on (When
switched from OFF to ON)
4
Refrigerant amount
adjustment
Normal control
Refrigerant
amount adjust-
ment mode
Anytime after power on (Will be dis-
abled 2 hours after compressor start
up except during initial start up mode)
5
-
-
-
-
6
-
-
-
-
7
Forced defrost
Normal control
Forced defrost
starts
Anytime after
power on (When
switched from
OFF to ON)
10 minutes after
compressor start-
up
8
Defrost timer setting
50 minutes
90 minutes
Anytime after power on (When
switched from OFF to ON)
9
-
-
-
-
10
-
-
-
-
SW3
1
SW3-2 function: en-
abled/disabled
SW3-2 disabled
SW3-2 enabled
Anytime after power on
2
Test run mode: ON/
OFF
Stops all ICs
Sends a test-run
signal to all IC
After power on and when SW3-1 is
on.
3
Defrost start tempera-
ture
-10°C
(-8 °C for 500
model unit)
-7°C
(-5 °C for 500
model unit)
Anytime after power on
4
Defrost end tempera-
ture
10°C
( 7°C for 500
model unit)
15°C
(12°C for 500
model unit)
Anytime after power on (except dur-
ing defrost operation)
5
-
-
-
-
6
Pump down operation Normal control
Pump down oper-
ation
After power on and while compressor
is stopped
7
Target condensing
temperature on the
heating mode Tcm
49°C 53°C Anytime
after
power
on
8
-
-
-
-
9
-
-
-
-
10
-
-
-
-
Note: All are set to OFF at factory shipment. (* For PUY series, only the SW4-9 is set to ON.)
Unless otherwise specified, set the switch to OFF where indicated by "-," which may be set to a certain setting
for a reason.
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...