[1] Error code Lists
Error
Code
Prelimi-
nary
error
code
Error
(prelim-
inary)
detail
code
Error code definition
Searched unit
Notes
0403
4300
4305
01
05
(Note)
Serial communication error
O
1102
1202
-
Abnormal discharge air temperature,
Abnormal discharge temperature sensor
O
1301
-
-
Abnormal low pressure
O
1302
1402
-
Abnormal high pressure
O
1500
1600
-
Excessive or insufficient refrigerant
(Overflow of the accumulator)
O
-
1605
-
Preliminary suction pressure abnormality
O
2503
-
-
Drain pump failure
Float switch trip
O
4103
-
-
Reverse phase/open phase
O
4108
4158
-
Overcurrent protection (51C2) (No.2 Comp)
O
4109
-
-
Abnormal fan
O
4115
-
-
Power supply sync signal abnormality
Frequency abnormality
O
4220
4225
(Note)
4320
4325
(Note)
[108]
Bus voltage drop (S/W detection)
O
[109]
Bus voltage rise (S/W detection)
O
[110]
Bus voltage abnormality (H/W detection)
O
[111]
Logic error
O
4230
4235
(Note)
4330
4325
(Note)
-
Heatsink overheat protection (THHS abnormality)
O
4240
4245
(Note)
4340
4345
(Note)
-
Overload protection
O
4250
4255
(Note)
4350
4355
(Note)
[101]
IPM error
O
[102]
ACCT overcurrent breaker trip (H/W detection)
O
[103]
DCCT overcurrent breaker trip (H/W detection)
O
[104]
IPM short/grounding abnormality
O
[105]
Overcurrent error due to short-circuited motor
O
[106]
Instantaneous overcurrent breaker trip
(S/W detection)
O
[107]
Effective overcurrent breaker trip (S/W detection)
O
4260
4265
(Note)
436X
(No er-
ror his-
tory)
-
Cooling fan abnormality
O
Outdoor unit
Indoor unit
Remote controller
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...