- 71 -
[
VI
Refrigerant Circuit ]
2. Indoor unit
Part
name
Symbols
(functions)
Notes
Usage
Specifications
Check method
Linear ex-
pansion
valve
(LEV)
LEV
1. Adjusts superheat at the heat
exchanger outlet of the indoor
unit during cooling
2. Adjusts subcool at the heat
exchanger outlet of the indoor
unit during cooling
DC12V
Opening of a valve driven by
a stepping motor
0-(2000) pulses
Continuity check
with a tester
Continuity be-
tween white, red,
and orange.
Continuity be-
tween yellow,
brown, and blue.
Ther-
mistor
TH21
(Suction
air tem-
perature)
Indoor unit control (Thermo)
0°C : 15kohm
10°C :9.7kohm
20°C :6.4kohm
25°C :5.3kohm
30°C :4.3kohm
40°C :3.1kohm
Resistance check
TH22
(Pipe tem-
perature)
Indoor unit control (Freeze pre-
vention, Pre-heating stand-by)
TH23
(Gas pipe
tempera-
ture)
LEV control during cooling oper-
ation (Superheat detection)
TH24
(Dis-
charge air
tempera-
ture)
Controls indoor unit discharge
(thermostat)
Float
Switch
33P1
Detects drain pan water level
Contact Resistance:
Under 250 mohm
B contact type
Continuity check
with a tester
33P2
P500
model
only
Motor
MF
Sends air
PFD-P250VM-E
AC380~415V Type E 4P
Output 3.7kW
Rotation number
check
Standard 930rpm
PFD-P500VM-E
AC380~415V Type B 4P
Output 5.5kW
Rotation number
check
Standard 978rpm
Yellow
M
Blue
Brown
White
Red
Orange
R = 15k
0
R = 3460
R = 15
0/80
t
3460 273 t
1
273
1
exp
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...