- 24 -
[
II
Restrictions ]
2. System with two refrigerant circuits
Sample control wiring
Notes
Maximum allowable length
1.Assign the sequential number to the indoor units.
2.Do not connect the terminal blocks (TB5) on the indoor unit-
sthat are connected to different outdoor units with each oth-
er.
3.Replacement of male power supply switch connector(CN41)
must be performed only on one of the outdoor units.
4.Provide grounding to S terminal on the terminal block for-
transmission line for centralized control (TB7) on only one
ofthe outdoor units.
5.When the power supply unit is connected to the transmis-
sion line for centralized control, leave the male connector on
the female power supply switch connector (CN41) as it is.
(Factory setting)
(1) Indoor/outdoor transmission line
Maximum distance (1.25mm
2
or larger)
L1, L2 200m
(2) Transmission line for centralized control
Maximum line distance via outdoor unit
(1.25mm
2
or larger)
L1+L31+L2 500m
NO
NO
OC
TB3
TB7
M1M2
M1M2S
51
IC
TB5-1
A1 B1 S
01
TB5-2
A2 B2S
02
OC
TB3
TB7
S
52
A B
TB15
1 2
MA
L31
L1
L2
CN41
CN40
Replace
Connect
M1M2
M1M2
*Two indoor controllers (controller circuit boards)
are equipped in the indoor unit (P500).
Leave the male
connector on
CN41 as it is.
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...