- 23 -
[
II
Restrictions ]
Wiring method/address setting method
1) Indoor/outdoor transmission line
Connect M1, M2 terminals of the indoor/outdoor transmission line terminal block (TB3) on the outdoor unit (OC)
and A1, B1 terminals of the indoor/outdoor terminal block (TB5-1) on the indoor unit (IC). (Non-polarized 2-core
cable)
Only use shielded cables.
[Shielded cable connection]
Connect the earth terminal of the OC and S terminal of the IC terminal block (TB5-1).
2) Switch setting
Address setting is required as follows.
Pro-
ce-
dure
s
Unit or controller
Address-
settin-
grange
Setting method
Notes
Facto-
ry set-
ting
1
Indoor
unit
Main unit IC
01 to 50
Assign a sequential odd number
starting with "01" to the upper in-
door controller.
00
Sub unit
IC
01 to 50
Assign sequential numbers start-
ing with the address of the main
unit in the same group. (Main unit
a1)
2
Outdoor unit
OC
51 to 100
Add 50 to the address assigned to
the indoor unit connected to the
system with one outdoor unit.
00
3
MA
remote
controller
Main
remote
control-
ler
MA
No settings
required.
-
Main
Sub
remote
control-
ler
MA
Sub
remote
controller
Settings to be made with the sub/
main switch
Summary of Contents for PU(H)Y-P250YGM-A
Page 9: ......
Page 11: ... 2 ...
Page 23: ... 14 ...
Page 25: ... 16 ...
Page 41: ... 32 ...
Page 53: ... 44 ...
Page 67: ... 58 ...
Page 73: ... 64 ...
Page 81: ... 72 ...
Page 83: ... 74 ...
Page 105: ... 96 ...
Page 107: ... 98 ...
Page 117: ... 108 ...
Page 119: ... 110 ...
Page 183: ... 174 ...