5 - 54
MELSEC-Q
5 DATA USED FOR POSITIONING CONTROL
Item
Setting value, setting range
Default
value
Setting value buffer memory
address
Value set with peripheral
device
Value set with sequence program
Axis 1 Axis 2 Axis 3 Axis 4
Pr.53
OP shift amount
The setting value range differs depending on the " Pr.1 Unit setting".
Here, the value within the [Table 1] range is set.
0
84
85
234
235
384
385
534
535
Pr.54
OPR torque limit value
1 to 300 (%)
1 to 300 (%)
300
86
236
386
536
Pr.55
Deviation counter
clear signal output
time
1 to 65535 (ms)
1 to 65535 (ms)
1 to 32767:
Set the decimal value as it is.
32768 to 65535:
Convert into hexadecimal and set.
11 87
237
387
537
Pr.56
Speed designation
during OP shift
0 : OPR speed
0
0 88
238
388
538
1 : Creep speed
1
Pr.57
Dwell time during
OPR retry
0 to 65535 (ms)
0 to 65535 (ms)
0 to 32767 :
Set as a decimal
32768 to 65535 :
Convert into hexadecimal and set
0 89
239
389
539
Pr.53 OP shift amount
Set the amount to shift (move) from the position stopped at with machine OPR.
The OP shift function is used to compensate the OP position stopped at with
machine OPR.
If there is a physical limit to the OP position, due to the relation of the near-point
dog installation position, use this function to compensate the OP to an optimum
position.
OPR direction
When " OP
shift amount" is positive
Shift point
Shift point
When " OP
shift amount" is negative
Start point
Shift after deviation
counter clear is canceled
Near-point dog signal
Zero signal
Pr.53
Pr.53
Pr.44
Summary of Contents for D75D4
Page 2: ......
Page 22: ...A 20 MEMO ...
Page 24: ...MEMO ...
Page 41: ...1 17 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 48: ...1 24 MELSEC Q 1 PRODUCT OUTLINE MEMO ...
Page 58: ...2 10 MELSEC Q 2 SYSTEM CONFIGURATION MEMO ...
Page 65: ...3 7 MELSEC Q 3 SPECIFICATIONS AND FUNCTIONS ...
Page 139: ...5 35 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 238: ...5 134 MELSEC Q 5 DATA USED FOR POSITIONING CONTROL MEMO ...
Page 251: ...6 13 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 254: ...6 16 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 255: ...6 17 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 256: ...6 18 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 259: ...6 21 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 260: ...6 22 MELSEC Q 6 SEQUENCE PROGRAM USED FOR POSITIONING CONTROL ...
Page 292: ...7 8 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS ...
Page 294: ...7 10 MELSEC Q 7 MEMORY CONFIGURATION AND DATA PROCESS ...
Page 298: ...MEMO ...
Page 462: ...9 140 MELSEC Q 9 MAJOR POSITIONING CONTROL MEMO ...
Page 490: ...10 28 MELSEC Q 10 HIGH LEVEL POSITIONING CONTROL MEMO ...
Page 524: ...11 34 MELSEC Q 11 MANUAL CONTROL Creating the program ...
Page 666: ...14 24 MELSEC Q 14 DEDICATED INSTRUCTIONS MEMO ...
Page 675: ...15 9 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 716: ...15 50 MELSEC Q 15 TROUBLESHOOTING MEMO ...
Page 725: ...Appendix 9 MELSEC Q APPENDICES MEMO ...
Page 878: ...Appendix 162 MELSEC Q APPENDICES 6 QD75D4N 90 23 27 4 12 98 4 46 Unit mm ...
Page 879: ...Appendix 163 MELSEC Q APPENDICES 7 QD75P1 QD75P2 QD75P4 27 4 23 98 90 4 46 unit mm ...
Page 880: ...Appendix 164 MELSEC Q APPENDICES 8 QD75D1 QD75D2 QD75D4 27 4 23 90 12 98 4 46 unit mm ...
Page 893: ...WARRANTY ...
Page 895: ......