6. Connections of Control Unit
6.10 Connecting with Skip Signal (Sensor)
71
(2) Skip signal input conditions
The input signals must be used within the following condition ranges.
Input voltage at external contact ON
18V or more, 25.2V or less
Input current at external contact ON
6mA or more
Input voltage at external contact OFF
4V or less
Input current at external contact OFF
2mA or less
Input signal holding time (Ton)
2ms or more
Machine side contact capacity
30V or more, 16mA or more
<Related items>
Cable drawing: "Appendix 2 (FCUA-R030 cable)"
Connector pin assignment: "Appendix 3 (SKIP connector)"