KE600 Inverter Parameter Description
77
stronger electromagnetic interference.
If the carrier frequency is lower than the factory default, it is possible to cause less output torque of
motor and more harmonic current.
The effect of modifying carrier frequency is as following:
Carrier frequency
Low
→
High
Motor noise
High
→
Low
Output current waveform
Poor
→
Good
Motor temperature rise
High
→
Low
Inverter temperature rise
Low
→
High
Leakage current
Small
→
Big
External radiation interference
Small
→
Big
P0-16
Carrier frequency adjusting
according to temperature
Factory default
1
Setting range
0: No
1: Yes
The inverter can automatically adjust the carrier frequency according to its temperature. This function can
reduce the possibility of overheat alarm of the inverter.
P0-17
Acceleration time 1
Factory default
Model depend
Setting range
0.00s ~ 36000s
P0-18
Deceleration time 1
Factory default
Model depend
Setting range
0.00s ~ 36000s
Acceleration time is the time of accelerating from 0Hz to ACC/DEC time reference frequency (P0-25).
Deceleration time is the time of decelerating from ACC/DEC time reference frequency (P0-25) to 0Hz.
Please refer to following figure.
Setting deceleration time
Actual deceleration time
Setting acceleration time
Actual acceleration time
t1
t2
Fset
Fmax
time
Hz output frequency
Figure 6-1 ACC/DEC time diagram
There are totally four groups of acceleration/deceleration time which can be selected via the multifunctional
digital input terminals.
Group 1: P0-17, P0-18;