![Micno KE600 Series Manual Download Page 50](http://html1.mh-extra.com/html/micno/ke600-series/ke600-series_manual_1784752050.webp)
KE600 Inverter Function Parameter List
47
Function
code
Name
Detailed instruction
Factory
default
Modify
46: Speed control / torque control
switching
47: Emergency stop
48: External stop terminal 2
49: Deceleration DC braking
50: The running time reset
P4-10
Terminal filter time
0.000s ~ 1.000s
0.010s
○
P4-11
Terminal command mode
0: Two-line mode 1
1: Two-line mode 2
2: Three-line mode 1
3: Three-line mode 2
0
◎
P4-12
UP/DN change rate
0.001Hz/s ~ 50.000Hz/s
1.00Hz/s
○
P4-13
AI curve 1 minimum input
0.00V ~ P4-15
0.00V
○
P4-14
AI curve 1 minimum input
corresponding setting
-100.0% ~ +100.0%
0.0%
○
P4-15
AI curve 1 maximum input
P4-13 ~ +10.00V
10.00V
○
P4-16
AI curve 1 maximum input
corresponding setting
-100.0% ~ +100.0%
100.0%
○
P4-17
AI1 filter time
0.00s ~ 10.00s
0.10s
○
P4-18
AI curve 2 minimum input
0.00V ~ P4-20
0.00V
○
P4-19
AI curve 2 minimum input
corresponding setting
-100.0% ~ +100.0%
0.0%
○
P4-20
AI curve 2 maximum input
P4-18 ~ +10.00V
10.00V
○
P4-21
AI curve 2 maximum input
corresponding setting
-100.0% ~ +100.0%
100.0%
○
P4-22
AI2 filter time
0.00s ~ 10.00s
0.10s
○
P4-23
AI curve 3 minimum input
-10.00V ~ P4-25
-10.00V
○
P4-24
AI curve 3 minimum input
corresponding setting
-100.0% ~ +100.0%
0.0%
○
P4-25
AI curve 3 maximum input
P4-23 ~ +10.00V
10.00V
○
P4-26
AI curve 3 maximum input
corresponding setting
-100.0% ~ +100.0%
100.0%
○
P4-27
Keypad potentiometer
input filter time
0.00s ~ 10.00s
0.10s
○
P4-28
HDI minimum input
0.00kHz ~ P4-30
0.00kHz
○
P4-29
HDI minimum input
corresponding setting
-100.0% ~ 100.0%
0.0%
○
P4-30
HDI maximum input
P4-28 ~ 100.00kHz
50.00
kHz
○