KE600 Inverter Parameter Description
124
P8-41
Any arrival current 2 amplitude
Factory default
0.0%
Setting range
0.0% ~ 300.0% (motor rated current)
When the output current is in the range of positive or negative detection amplitude of setting any arrival
current, DO terminal outputs ON signal. KE600 series inverter provides two parameters of any arrival
current and detection amplitude.
Time (t)
Any arrival current
Any arrival current amplitude
OFF
OFF
ON
ON
ON
OFF
Any arrival current detection
signal DO or Relay
Any arrival current amplitude
Output current
Figure 6-22 Any arrival current detection diagram
P8-42
Timing function selection
Factory default
0
Setting range
0
Invalid
1
Valid
P8-43
Timing running time selection
Factory default
0
Setting range
0
P8-44
1
AI1
2
AI2
3
Keypad potentiometer
P8-44 Analog input scale 100% corresponds to P8-44
P8-44
Timing running time
Factory default
0.0Min
Setting range
0.0Min ~ 3600.0Min
The parameters are used to set the inverter timing running function.
When P8-42 timing function selection is valid, timing starts after the inverter starts, reaches the setting
timing running time, the inverter stops automatically, meantime, DO terminal outputs ON signal.
Timing starts from 0 when the inverter starts, timing remain running time can be viewed via U0-20.
The timing running time is set by P8-43, P8-44, time unit is minute.