KE600 Inverter Parameter Description
157
or torque fluctuation is bigger, the proportional gain and the Integral gain should be decreased manually.
A2-61
Control mode
Factory default
0
Setting range
0
V/F control
1
Sensorless vector control
0: V/F control
It is suitable for general purpose application such as pumps, fans etc. One inverter can drive multiple
motors.
1: Sensorless vector control
It is widely used for the application which requires high torque at low speed, high speed accuracy, and
quicker dynamic response, such as machine tool, injection molding machine, centrifugal machine and
wire-drawing machine, etc.