KE600 Inverter Parameter Description
104
P5-09
HDO output maximum frequency
Factory default
50.00kHz
Setting range
0.01kHz ~ 100.00kHz
When HDO terminal is selected as pulse output, this code is used to set the maximum frequency of output
pulse.
P5-10
AO1 Zero-offset coefficient
Factory default
0.0%
Setting range
-100.0% ~ +100.0%
P5-11
AO1 gain
Factory default
1.00
Setting range
-10.00 ~ +10.00
P5-12
AO2 Zero-offset coefficient
Factory default
0.00%
Setting range
-100.0% ~ +100.0%
P5-13
AO2 gain
Factory default
1.00
Setting range
-10.00 ~ +10.00
The parameters are used to correct the zero drift of the analog output and the output amplitude deviation.
They can also be used to define custom AO output curve.
If “b” represents zero offset, k represents gain, Y represents actual output, and X represents standard
output, the actual output is: Y=kX+b;
Where,
100% of zero-offset coefficients of AO1 and AO2 correspond to 10V (or 20mA).
Standard output denotes 0 to maximum analog output corresponding to the output of 0 to 10V (or 4mA to
20mA) without Zero-offset and gain correction.
P5-17
HDO open collector output delay time
Factory default
0.0s
Setting range
0.0s ~ 3600.0s
P5-18
Relay 1 output delay time
Factory default
0.0s
Setting range
0.0s ~ 3600.0s
P5-19
Relay 2 output delay time
Factory default
0.0s
Setting range
0.0s ~ 3600.0s
P5-20
Y1 output delay time
Factory default
0.0s
Setting range
0.0s ~ 3600.0s
P5-21
Y2 output delay time
Factory default
0.0s
Setting range
0.0s ~ 3600.0s
Set the delay time of output terminal HDO, relay 1 and relay 2. The delay time is time interval from the
status changing to actual output changing.