KE600 Inverter Function Parameter List
48
Function
code
Name
Detailed instruction
Factory
default
Modify
P4-31
HDI maximum input
corresponding setting
-100.0% ~ 100.0%
100.0%
○
P4-32
HDI filter time
0.00s ~ 10.00s
0.10s
○
P4-33
AI curve selection
Units place: AI1
1: Curve 1 (see P4-13 ~ P4-16)
2: Curve 2 (see P4-18 ~ P4-21)
3: Curve 3 (see P4-23 ~ P4-26)
Tens place: AI2, ibid
321
○
P4-34
AI below minimum input
setting selection
Units place: AI1
0: Correspond to minimum input
setting
1: 0.0%
Tens place: AI2, ibid
Hundreds place: Keypad
potentiometer, ibid
000
○
P4-35
D1 delay time
0.0s ~ 3600.0s
0.0s
◎
P4-36
D2 delay time
0.0s ~ 3600.0s
0.0s
◎
P4-37
D3 delay time
0.0s ~ 3600.0s
0.0s
◎
P4-38
DI terminal valid mode
selection 1
0: Active-high
1: Active-low
Units place: D1
Tens place: D2
Hundreds place: D3
Thousands place: D4
Ten thousands place: D5
00000
◎
P4-39
DI terminal valid mode
selection 2
0: Active-high
1: Active-low
Units place: D6
Tens place: HDI
00
◎
P5 Group: Output Terminal
P5-00
HDO terminal output
mode selection
0: High speed pulse output
1: Open collector output
0
○
P5-01
HDO open collector
output selection
0: No output
1: Inverter is running
2: Fault output (fault stop)
3: FDT1 output
4: Frequency arrival
5: Zero-speed running (no output
when stop)
6: Motor overload pre-alarm
7: Inverter overload pre-alarm
0
○
P5-02
Relay T1 output selection
2
○
P5-03
Relay T2 output selection
0
○
P5-04
Y1 output selection
0
○