KE600 Inverter Parameter Description
71
Chapter 6 Parameter Description
Group P0 Basic Function
P0-00
Inverter model
Factory default
1
Setting range
1
G model
1: G model: Applicable to constant torque load.
KE600 series inverter is only suitable for G mode, for constant torque load.
P0-01
Control mode
Factory default
0
Setting range
0
V/F control
1
Sensorless vector control
2
Close-loop vector control
0: V/F control
It is suitable for general purpose application such as pumps, fans etc. One inverter can drive multiple
motors.
1: Sensorless vector control
It is widely used for the application which requires high torque at low speed, high speed accuracy, and
quicker dynamic response, such as machine tool, injection molding machine, centrifugal machine and
wire-drawing machine, etc.
2, Close-loop vector control
The motor must fix an encoder, the inverter has to fix an additional PG card which matches with the
encoder. It is suitable for the applications which need high accurate speed control or torque control. One
inverter can drive only one motor. The applications are paper making machine, hoist machine, elevator etc.
Note:
1, The autotuning of motor parameters must be accomplished properly if you use the sensorless vector
control. How to autotuning of motor parameters please refer to P4 Group.
In order to achieve better control characteristic, the parameters of vector control (P2 Group) should be
adjusted.
2, If close-loop vector control mode is selected, it should also set correct parameter of encoder like
encoder resolution, encoder type etc.
P0-02
Running Command source
Factory default
0
Setting range
0
0: Keypad (LED OFF)
1
1: Terminal (LED ON)
2
2: Communication (LED flickers)
Select the input channel for control command. The inverter control commands include start, stop, forward
run, reverse run, Jog and so on.