![Micno KE600 Series Manual Download Page 173](http://html1.mh-extra.com/html/micno/ke600-series/ke600-series_manual_1784752173.webp)
KE600 Inverter Trouble Shooting
170
Fault Name
Over-voltage when deceleration
Fault Code
E-06
Reason
1. The input voltage is too high
2. There is external force driving the motor to run during deceleration
3. The deceleration time is too short
4. Have not installed braking unit and braking resistor
Solution
1. Make the voltage in the normal range
2. Cancel the external force
3. Increase the deceleration time
4. Install braking unit and braking resistor
Fault Name
Over-voltage when constant speed running
Fault Code
E-07
Reason
1. The input voltage is too high
2. There is external force driving the motor to run during the inverter running
Solution
1. Make the voltage in the normal range
2. Cancel the external force or install braking resistor
Fault Name
Power-supply fault
Fault Code
E-08
Reason
1. The input voltage is out of range
Solution
1. Make the voltage in the normal range
Fault Name
Under-voltage fault
Fault Code
E-09
Reason
1. Instantaneous power-off
2. The input voltage is out of range
3. Bus voltage is abnormal
4. The rectifier bridge and buffer resistor are abnormal
5. The power board is abnormal
6. The control board is abnormal
Solution
1. Fault Reset
2. Make the voltage in the normal range
3. Ask for technical support
4. Ask for technical support
5. Ask for technical support
6. Ask for technical support