KE600 Inverter Parameter Description
100
P4-38
DI terminal valid mode selection 1
Factory default
00000
Setting range
Units place
DI1 terminal valid status setting
0
Active-high
1
Active-low
Tens place
D2 terminal valid status setting (0 ~ 1, ibid)
Hundreds place
D3 terminal valid status setting (0 ~ 1, ibid)
Thousands place
D4 terminal valid status setting (0 ~ 1, ibid)
Ten thousands place
D5 terminal valid status setting (0 ~ 1, ibid)
P4-39
DI terminal active mode selection 2
Factory default
00
Setting range
Units place
D6 terminal valid status setting
0
Active-high
1
Active-low
Tens place
D7 / HDI terminal valid status setting (0 ~ 1,
ibid)
Hundreds place
D8 terminal valid status setting (0 ~ 1, ibid)
Thousands place
D9 terminal valid status setting (0 ~ 1, ibid)
Ten thousands place D10 terminal valid status setting (0 ~ 1, ibid)
They are used to set the digital input terminal active status mode. If the selection is active-high, the
relevant DI terminal connects with COM is valid, disconnect invalid. If the selection is active-high, the
relevant DI terminal connects with COM is invalid, disconnect valid.