KE600 Inverter Parameter Description
117
Group P8 Enhanced Function
P8-00
Jog running frequency
Factory default
2.00Hz
Setting range
0.00Hz ~ P0-10 (maximum frequency)
P8-01
Jog acceleration time
Factory default
20.0s
Setting range
0.1s ~ 3600.0s
P8-02
Jog deceleration time
Factory default
20.0s
Setting range
0.1s ~ 3600.0s
It is used to define the reference frequency and ACC/DEC time of the inverter when jogging.
During Jog running, the start mode is fixed to direct start (P6-00=0), the stop mode is fixed to deceleration
to stop (P6-10=0).
P8-03
Acceleration time 2
Factory default
Model depend
Setting range
0.1s ~ 3600.0s
P8-04
Deceleration time 2
Factory default
Model depend
Setting range
0.1s ~ 3600.0s
P8-05
Acceleration time 3
Factory default
Model depend
Setting range
0.1s ~ 3600.0s
P8-06
Deceleration time 3
Factory default
Model depend
Setting range
0.1s ~ 3600.0s
P8-07
Acceleration time 4
Factory default
Model depend
Setting range
0.1s ~ 3600.0s
P8-08
Deceleration time 4
Factory default
Model depend
Setting range
0.1s ~ 3600.0s
KE600 series inverter supplies 4 kinds of ACC/DEC time. The principles of them are the same. Please
refer to description of P0-17 and P0-18 for more details.
User can select the one of 4 kinds ACC/DEC time thought the different combination of DI terminals. See
the description of P4-00~P4-05, then pay attention to Function (16) & Function (17) and Attached table 2.
P8-09
Jump frequency 1
Factory default
0.00Hz
Setting range
0.00Hz ~ P0-10 (maximum frequency)
P8-10
Jump frequency 2
Factory default
0.00Hz
Setting range
0.00Hz ~ P0-10 (maximum frequency)
P8-11
Jump frequency amplitude
Factory default
0.00Hz
Setting range
0.00 ~ P0-10 (maximum frequency)
By means of setting jump frequency, the inverter can keep away from the mechanical resonance with the
load. P8.09 and P8.10 are center value of frequency to be skipped.
If both P8-09 and P8-10 are 0, the jump frequency function is invalid no matter what P8.11 is.