KE600 Inverter Parameter Description
123
Zero current detection
delay time
P8-35
Zero current
detection signal
Zero current detection
level
P8-34
Output current
Time (t)
Time (t)
Figure 6-20 Zero-current detection diagram
P8-36
Output current over limit value
Factory default
200.0%
Setting range
0.0% (No detection)
0.1% ~ 300.0% (motor rated current)
P8-37
Output current over limit detection delay time
Factory default
0.00s
Setting range
0.00s ~ 360.00s
When the output current is bigger than or over-limit detection point, lasts for longer than software over
current point detection delay time, DO terminal outputs ON signal.
Output current over
limit value
P8-36
Output current
Output current over
limit detection signal
Time (t)
Time (t)
Output current over
limit detection delay
time P8-37
Figure 6-21 Output current over limit function diagram
P8-38
Any arrival current 1
Factory default
100.0%
Setting range
0.0% ~ 300.0% (motor rated current)
P8-39
Any arrival current 1 amplitude
Factory default
0.0%
Setting range
0.0% ~ 300.0% (motor rated current)
P8-40
Any arrival current 2
Factory default
100.0%
Setting range
0.0% ~ 300.0% (motor rated current)