![Micno KE600 Series Manual Download Page 156](http://html1.mh-extra.com/html/micno/ke600-series/ke600-series_manual_1784752156.webp)
KE600 Inverter Parameter Description
153
A2-06 ~ A2-10 as standard Y series motor parameters.
If motor parameters autotuning cannot be performed on the site, please input the related parameters
provided by the motor manufacturer.
A2-11
Motor parameters autotuning
Factory default
0
Setting range
0
No operation
1
Static autotuning
2
Rotation autotuning
0: No operation, prohibit motor parameter autotuning.
1: Motor parameter static autotuning, suitable for the applications which the asynchronous motor is not
easy to disconnect with the load, and cannot make rotation autotuning.
Before performing static autotuning, please set the motor type and motor parameters (A2-00 ~ A2-05)
correctly. The inverter can obtain A2-06 ~ A2-08 via static autotuning.
Action description: Set the function code to be 1, the keypad displays “TUNE”, then press RUN key, the
inverter will make static autotuning.
2: Motor parameter rotation autotuning
To ensure the dynamic control performance of inverter, please select rotation autotuning. During the
rotation autotuning, the motor must be disconnected with the load (i.e. no-load).
During rotation autotuning, the inverter will make static autotuning at first, and then accelerates to 80%
motor rated frequency according to acceleration time P0-17, holding for a while, at last decelerates to stop
according to deceleration time P0-18 and finish autotuning.
Before rotation autotuning, please set motor type and motor parameters P1-00 ~ P1-05, during rotation
autotuning, the inverter can obtain P1-06~P1-10, vector control current loop PI parameters P2-13 ~ P2-16.
Action description: Set the function code to 2, the keypad displays “TUNE”, then press RUN key, the
inverter will make rotation autotuning.
Note: Autotuning is valid only on keypad operation mode, cannot make autotuning under terminal
and communication operation modes.
A2-27
Encoder resolution
Factory default
1024
Setting range
0~10000
Set the pulse quantity while the motor run one cycle.
Under the close-loop vector control mode, the encoder resolution has to be set correctly, otherwise, the
motor cannot run normally.
A2-28
Encoder type
Factory default
0
Setting range
0: ABZ incremental encoder
KE600 is only suitable for ABZ incremental encoder.