KE600 Inverter Mechanical and Electric Installation
24
3.1.2 Heat dissipation should be taken into account during the mechanical installation. Please pay
attention the following items:
1) Install the inverter vertically so that the heat may be expelled from the top. However, the equipment
cannot be installed upside down. If there are multiple inverters, parallel installation is a better choice. In
applications where the upper and lower inverters need to be installed, please refer to Figure 3-
1 “KE600
Series Inverter
Installation Diagram” and install an insulating splitter.
2) The mounting space should be as indicated as Figure 3-1, so as to ensure the heat dissipation space of
the inverter. However, the heat dissipation of other devices in the cabinet should also be taken into
account.
3) The installation bracket must be flame retardant.
4) In the applications where there are metal dusts, it is recommended to mount the radiator outside the
cabinet. In this case, the space in the sealed cabinet should be large enough.
3.2 Electrical Installation
3.2.1 Guide to the external electrical parts
Table 3-1 Selection Guide of External Electrical Parts of KE600 Series Inverter
Inverter Model
Circuit Breaker
(MCCB)
A
Recommended
Contactor
A
Recommended
Conducting
Wire of Main
Circuit at Input
Side
mm
2
Recommended
Conducting
Wire of Main
Circuit at
Output Side
mm
2
Recommended
Conducting
Wire of Control
Circuit
mm
2
3AC 220~240V
KE600-1R5G-T2
16
10
2.5
2.5
1.0
KE600-2R2G-T2
25
16
4.0
4.0
1.0
KE600-004G-T2
32
25
4.0
4.0
1.0
KE600-5R5G-T2
63
40
4.0
4.0
1.0
KE600-7R5G-T2
63
40
6.0
6.0
1.0
KE600-011G-T2
100
63
10
10
1.5
KE600-015G-T2
125
100
16
10
1.5
KE600-018G-T2
160
100
16
16
1.5
KE600-022G-T2
200
125
25
25
1.5
KE600-030G-T2
200
125
35
25
1.5
KE600-037G-T2
250
160
50
35
1.5
KE600-045G-T2
250
160
70
35
1.5
KE600-055G-T2
350
350
120
120
1.5
KE600-075G-T2
500
400
185
185
1.5