KE600 Inverter Parameter Description
141
The wobble amplitude is relative to the central frequency (variable wobble amplitude, select PB-00=0):
wobble amplitude: AW=frequency source: P0-07 × wobble amplitude: PB-01.
The wobble amplitude is relative to the maximum frequency (fixed wobble amplitude, select PB-00=1):
wobble amplitude: AW=maximum frequency: P0-10 × wobble amplitude: PB-01.
Sudden jump frequency=wobble amplitude: AW × sudden jump frequency amplitude: PB-02. That is the
value of sudden jump frequency relative to the wobble amplitude when the wobble frequency is running.
If the wobble amplitude relative to the central frequency (variable wobble amplitude, select PB-00=0) is
selected, the sudden jump frequency is a variable value.
If the wobble amplitude relative to the maximum frequency (fixed wobble amplitude, select PB-00=1) is
selected, the sudden jump frequency is a fixed value.
PB-03
Wobble frequency cycle
Factory default
10.0s
Setting range
0.1s ~ 3000.0s
PB-04
Triangle-wave rise time of wobble
frequency
Factory default
50.0%
Setting range
0.1% ~ 100.0%
Wobble frequency cycle: It refers to the time of a complete cycle of wobble frequency.
PB-04 is relative to the percentage of PB-03.
Triangular wave rise time = PB-03 × PB-04 (unit: s)
Triangular wave fall time = PB-03 × (1-PB-04) (unit: s)
PB-05
Setting length
Factory default
1000m
Setting range
0m ~ 65535m
PB-06
Actual length
Factory default
0m
Setting range
0m ~ 65535m
PB-07
Number of pulses per meter
Factory default
100.0
Setting range
0.1 ~ 6553.5
The parameters are used in fixed length control.
Length information can be collected via input terminals, PB-06= the collected number of pulses/PB-07.
When PB-06 is longer than PB-
05, DO outputs “length arrival” ON signal.
During fixed length control, length reset operation can be done by set DI terminal function to 28, refers to
P4-00~P4-06 for details.
The relative input terminal function need to be set to 27 (length counting input) for applications, HDI must
be used when the pulse frequency is high.
PB-08
Setting counting value
Factory default
1000
Setting range
1 ~ 65535
PB-09
Designated counting value
Factory default
1000
Setting range
1 ~ 65535
The counting value can be collected via digital input terminals. The relative input terminal function need to
be set to 25 (Counter input) for applications, HDI must be used when the pulse frequency is high.