MI 2883 Energy Master
Operating the instrument
85
Connection check
Check if measurement results comply with given limits.
Measurement will be marked with OK sign ( ) if
measurement results are within following limits:
Voltage: 90% ÷ 110% of nominal voltage
Current: 10% ÷ 110% of nominal current (Current clamp
range)
Frequency: 42.5 ÷ 57.5 Hz for 50Hz and 51 ÷ 69 Hz for
60Hz system frequency
U-
I Phase angle: ±90
0
Voltage and current sequence: 1
– 2 – 3
Each measurement, which is not within those limits, will
be market with Fail sign ( ).
Default parameters
Set factory default parameters. These are:
Nominal voltage: 230V (L-N);
Voltage ratio: 1:1;
Δ
:
1
Phase current clamps: Smart Clamps;
Neutral current clamps: None;
Connection: 4W;
Synchronization: U1
System frequency: 50 Hz.
Dip voltage: 90 % U
Nom
Dip hysteresis: 2 % U
Nom
Interrupt voltage: 5 % U
Nom
Interrupt hysteresis: 2 % U
Nom
Swell voltage: 110 % U
Nom
Swell hysteresis: 2 % U
Nom
Signalling frequency1: 316 Hz
Signalling frequency2:1060 Hz
Signalling record duration: 10 sec
Signalling threshold: 5 % of nominal voltage
RVC threshold: 3 % of nominal voltage
RVC hysteresis: 25 % of RVC threshold
Clear Alarm setup table