MI 2883 Energy Master
Recording Practice and Instrument Connection
101
Time Interval for data aggregation (Integration Period)
Include events and alarms capture if necessary
Recording start time (optional)
After setting recorder, recording can be started. (see section 3.14 for recorder
details).
Note:
Available memory status in Recorder setup should be checked before starting
recording. Max. recording duration and max. number of records are automatically
calculated according to recorder setup and memory size.
Note:
Recording usually last few days. Assure that instrument during recording session
is not reachable to the unauthorized persons. If necessary use LOCK functionality
described in section 3.20.5.
Note:
If during record session instrument batteries are drained, due to long interruption
for example, instrument will shut down. After electricity comes back, instrument will
automatically start new recording session.
Step 6: Measurement conclusion
Before leaving measurement site we need to:
Preliminary evaluate recorded data using TREND screens.
Stop recorder.
Assure that we record and measure everything we needed.
Step 7: Report generation (PowerView v3.0)
Download records using PC software PowerView v3.0 perform analysis and create
reports. See PowerView v3.0 manual for details.
4.2 Connection setup
4.2.1 Connection to the LV Power Systems
This instrument can be connected to the 3-phase and single phase network.
The actual connection scheme has to be defined in CONNECTION SETUP menu (see
Figure below).
Figure 4.2: Connection setup menu