MI 2883 Energy Master
Technical specifications
157
With iron clamps
A 1281 / 1000 A
±1.0 %
S
*Accuracy values are valid if cos
φ
0.80, I
10 % I
Nom
and U
80 % U
Nom
**Accuracy values are valid if sin
φ
0.50, I
10 % I
Nom
and U
80 % U
Nom
***Accuracy values are valid if cos
φ
0.50, I
10 % I
Nom
and U
80 % U
Nom
6.2.8 Fundamental power
Fundamental power
Measuring range
Accuracy
Active fundamental
power* (W)
Pfund
1
, Pfund
2
,
Pfund
3
, P
+
tot
0.000 k ÷ 999.9 M
4 digits
Excluding clamps
(Instrument only)
±0.5 %
Pfund
With flex clamps
A 1227 / 3000 A
A 1446 / 6000 A
±2.0 %
Pfund
With iron clamps
A 1281 / 1000 A
±1.0 %
Pfund
Reactive fundamental
power** (var)
Qfund
1
, Qfund
2
,
Qfund
3
, Q
+
tot
0.000 k ÷ 999.9 M
4 digits
Excluding clamps
(Instrument only)
±0.5 %
Qfund
With flex clamps
A 1227 / 3000 A
A 1446 / 6000 A
±2.0 %
Qfund
With iron clamps
A 1281 / 1000 A
±1.0 %
Qfund
Apparent fundamental
power*** (VA)
Sfund
1
, Sfund
2
,
Sfund
3
, S
+
tot
0.000 k ÷ 999.9 M
4 digits
Excluding clamps
(Instrument only)
±0.5 %
Sfund
With flex clamps
A 1227 / 3000 A
A 1446 / 6000 A
±2.0 %
Sfund
With iron clamps
A 1281 / 1000 A
±1.0 %
Sfund
*Accuracy values are valid if cos
φ
0.80, I
10 % I
Nom
and U
80 % U
Nom
**Accuracy values are valid if sin
φ
0.50, I
10 % I
Nom
and U
80 % U
Nom
***Accuracy values are valid if cos
φ
0.50, I
10 % I
Nom
and U
80 % U
Nom
6.2.9 Nonfundamental power
Nonfundamental
power
Measuring range
Conditions
Accuracy