Measuring range
Resolution
Accuracy
0 % I
N
om
< THD
I
< 100 % I
N
om
0.1 %
± 0.6
100 % I
N
om
< THD
I
< 200 % I
N
om
0.1 %
± 0.3
I
N
om
: Nominal current (RMS)
Measuring range
Resolution
Accuracy
0 < k < 200
0.1
± 0.6
6.2.15
Voltage interharmonics
Measuring range
Resolution
Accuracy
Uih
N
< 3 % U
Nom
10 mV
± 0.15 %
U
Nom
3 % U
Nom
< Uih
N
< 20 % U
Nom
10 mV
± 5 %
Uih
N
U
Nom
: nominal voltage (RMS)
Uih
N
: measured harmonic voltage
N
:
interharmonic component 0
th
÷ 50
th
6.2.16
Current interharmonics
Measuring range
Resolution
Accuracy
Ih
N
< 10 % I
N
om
10 mV
± 0.15 %
I
Nom
10 % I
N
om
< Ih
N
< 100 %
10 mV
± 5 %
Iih
N
I
N
om
: Nominal current (RMS)
Iih
N
: measured interharmonic current
N
:
interharmonic component 0
th
÷ 50
th
6.2.17
Signalling
Measuring range
Resolution
Accuracy
1 % U
N
om
< U
Sig
< 3 % U
N
om
10 mV
± 0.15 %
U
N
om
3 % U
N
om
< U
Sig
< 20 % U
Nom
10 mV
± 5 %
U
Sig
U
N
om
: Nominal current (RMS)
U
Sig
: Measured signalling voltage
6.2.18
Unbalance
Unbalance range
Resolution
Accuracy
u
-
0.5 % ÷ 5.0 %
0.1 %
± 0.3 %
± 0.3 %
u
0
i
-
0.0 % ÷ 20 %
0.1 %
± 1 %
± 1 %
i
0
6.2.19
Overdeviation and Underdeviation
Measuring range
Resolution
Accuracy
U
Over
0 ÷ 50 % U
Nom
0.001 %
± 0.15 %
U
Under
0 ÷ 90 % U
Nom
0.001 %
± 0.15 %