MI 2883 Energy Master
Operating the instrument
37
S1, S2, S3, S+
View:
Fundamental
power
Maximal ( ), average ( ) and minimal ( ) value of fundamental
apparent power (
Sfund
1
, Sfund
2
, Sfund
3
, S
+
tot
) for time interval
(IP) selected by cursor.
PFi1
±, PFi2±,
PFi3
±, PFit±
View:
Combined
power
Maximal ( ), average ( ) and minimal ( ) value of inductive
power factor (1
st
quadrant: PF
1ind
+
, PF
2ind
+
, PF
3ind
+
, PF
totind
+
and 3
rd
quadrant: PF
1ind
-
, PF
2ind
-
, PF
3ind
-
, PF
totind
-
) for time interval (IP)
selected by cursor.
PFc1
±, PFc2±,
PFc3
±, PFct±
View:
Combined
power
Maximal ( ), average ( ) and minimal ( ) value of capacitive
power factor (4
th
quadrant: PF
1cap
+
, PF
2cap
+
, PF
3cap
+
, PF
totcap
+
and
2
nd
quadrant: PF
1cap
-
, PF
2cap
-
, PF
3cap
-
, PF
totcap
-
) for time interval
(IP) selected by cursor.
Qi1
±, Qi2±, Qi3±,
Q+i
±
View:
Fundamental
power
Maximal ( ), average ( ) and minimal ( ) value of consumed
(Q
1ind
+
, Q
2ind
+
, Q
3ind
+
,
Q
+
totind
+
) or generated (Q
1ind
-
, Q
2ind
-
, Q
3ind
-
,
Q
+
totind
-
) fundamental reactive inductive power for time interval (IP)
selected by cursor.
Qc1
±, Qc2±,
Qc3
±, Q+c±
View:
Fundamental
power
Maximal ( ), average ( ) and minimal ( ) value of consumed
(Q
1cap
+
, Q
2cap
+
, Q
3cap
+
,
Q
+
captot
+
) or generated (Q
1cap
-
, Q
2cap
-
, Q
3cap
-
,
Q
+
captot
-
) fundamental reactive capacitive power for time interval
(IP) selected by cursor.
DPFi1
±,
DPFi2
±,
DPFi3
±
DPF+it
±
View:
Fundamental
power
Maximal ( ), average ( ) and minimal ( ) value of inductive
displacement power factor (1
st
quadrant: DPF
1ind
+
, DPF
2ind
+
,
DPF
3ind
+
, DPF
totind
+
, and 3
rd
quadrant: DPF
1ind
-
, DPF
2ind
-
, DPF
3ind
-
DPF
totind
-
,) for time interval (IP) selected by cursor.
DPFc1
±,
DPFc2
±,
DPFc3
±
DPF+ct
±
View:
Fundamental
power
Maximal ( ), average ( ) and minimal ( ) value of capacitive
displacement power factor (4
th
quadrant: DPF
1cap
+
, DPF
2cap
+
,
DPF
3cap
+
, DPF
totcap
+
, and 2
nd
quadrant: DPF
1cap
-
, DPF
2cap
-
,
DPF
3cap
-
, DPF
totcap
+
) for time interval (IP) selected by cursor.
Sn1, Sn2,
Sn3, Sen
View:
Nonfundamental
power
Maximal ( ), average ( ) and minimal ( ) value of consumed or
generated nonfundamental apparent power (
Sɴ
1
, Sɴ
2
, Sɴ
3
, Seɴ
tot
)
for time interval (IP) selected by cursor.
Di1, Di2,
Di3, Dei
View:
Nonfundamental
power
Maximal ( ), average ( ) and minimal ( ) value of consumed or
generated phase current distortion power
(Dı
1
, Dı
2
, Dı
3
, Deı
tot
) for
time interval (IP) selected by cursor.
Dv1, Dv2,
Dv3, Dev
View:
Nonfundamental
power
Maximal ( ), average ( ) and minimal ( ) value of consumed or
generated phase voltage distortion power (Dv
1
, Dv
2
, Dv
3
, Dev
tot
)
for time interval (IP) selected by cursor.
Ph1
±, Ph2±,
Ph3
±, Pht±
View:
Nonfundamental
power
Maximal ( ), average ( ) and minimal ( ) value of consumed