CVM-MINI-Ethernet

 

 

 

 

 

 

M98240101-03-18A 

 

POWER ANALYZER 

 

CVM-MINI-Ethernet

 

  

 

 

This manual is a quick guide to the use and operation of 

the 

CVM-MINI-ITF

 & 

CMV-MINI-MC

 with Ethernet 

connection. For more information, the whole manual 

may be downloaded from CIRCUTOR's web page: 

www.circutor.es

 

 

 Before any maintenance, modification to the 

connections, repair, etc., the equipment must be 

disconnected from the supply. If any operation or 

protection fault is suspected the equipment must 

remain out of service  ensuring against any accidental 

reconnection. The equipment is designed to be changed quickly 

in the event of any breakdown. 

 

 

The 

CVM-MINI

  is an instrument which measures, 

calculates and displays the main electrical parameters 

for three-phase industrial  systems (balanced or 

unbalanced). Measurements are in true effective value, 

via three AC voltage inputs and three AC. current 

inputs. (via 

I

/ 5 A or 1 A the 

ITF

 version and 

I

n

  0,25A  

MC 

version). The parameters measured and calculated 

are shown in the variables table, paragraph 7.

 

 

1.-  INSTALLATION 

The equipment is mounted on DIN rail. Also the device 

has to be provided of an magnetic-thermal switch to be 

disconnected. The fuses has to be type gl (IEC 269) or 

type M between 0,5 to 2 A. 

2.-  ETHERNET NETWORK SETUP 

The configuration software, IPSETUP.EXE, is available 

from the 

CIRCUTOR

  Web site. It  must be executed 

under Windows operative system. Once executed it will 

appear the following screen 

 

In the field "

MAC

" it must be typed the physical address 

of the unit  using scripts as separator, this data is 

showed on to the lateral label of the equipment and the 

format is 14:A6:2C:XX:XX:XX. 

In to the field "

Dirección

",  type the assigned IP 

address to the equipment into the local area network 

Into the field "

Netmask

" type the mask for the network. 

 In case of routing the equipment in a different network, 

setup the field "

Gateway

" with the IP address of the 

device that allows the route. For example, if the 

equipment must be accessible from Internet, will be 

necessary setup the IP address for the ADSL router 

that allows the Internet connection. Also the router will 

need convenient programming to allow Internet enroute 

and enable the traffic from/to the 

CVM-MINI-Ethernet

If it is not the case leave the filed "Gateway" in blank. 

 

3.-  DHCP IP assignment 

To assign the DHCP name, choose this option using 

the arrow on the upper right, and select “

On”

. Once the 

configuration fields have been enabled, enter the 

MAC”

 address that can be seen on the permanent side 

label attached to the  device, the format of which is 

14:A6:2C:XX:XX:XX

. In the “

Dirección”

  field, enter an 

unused, temporary IP address, which is within the 

working range of your computer. In the “

Host Name”

 

field, enter the 

DHCP

  name to be assigned to the 

equipment. Optionally, the user can configure the 

parameters of the “

ClientID

”  field.  The default 

VendorID”

 of the device is 

CIRCUTOR

 

Once the parameters have been configured click on 

"

Configurar

If the equipment is detected into the Ethernet network, 

it will appear the following screen. 

 

By clicking "

Aceptar

" the internal setup WEB page of 

the equipment will be displayed. 

 

If the equipment is not detected on the local network it 

will appear the following screen. 

 

Review the settings assigned to the computer, check 

the connection to the router and the Ethernet 

Connector LEDs are lit and / or blink. The LED on the 

left side of the connector is the link status and the LED 

on the right side indicates activity receive / transmit TX 

/ RX. Both can be lit in  green or amber color. If 

everything appears correct, consult with your admin for 

the local area network. 

 

 

 

 

 

4.-  SETTING (SETUP menu)  

(Press SETUP key for 5 seconds) 

 

The 

 

key validates the information and moves 

on to the next menu. 

 

The 

 max

  key allows the different options in a 

menu to be selected or increases a digit where a 

variable is being entered. 

 

The 

min

  key is used to move the cursor 

among the digits. 

 

The different options are sequentially described below. 

 

4.1.- Voltage transformer primary 

On screen the words  "

SET PriU

" appear followed by 6 

digits. These allow the voltage transformer primary to be 
set (from 

1

 to 

100,000

). 

4.2.- Voltage transformer secondary 

On screen the words "

SET SEcU

" appear followed by 3 digits. 

These allow the voltage transformer secondary to be set (from 

1

  to 

999

). 

4.3.-  Current transformer primary 

The display show "

SET PriA

" followed by 5 digits. These allow 

the current transformer primary to be set (from 

1

 to 

10,000

).   

In the case of using a transforming system type MC1, 

introduces the primary of the transformer 

corresponding to the relation of the selected physical 

wiring. In case of using type MC3, introduces the value 

of the primary that appears in the label of the 

transformer. 

4.4.- Current transformer secondary. 

The display show "

SET SecA

". In the 

ITF

 versions, selection is 

allowed between 1 and 5 A. In the 

MC

 version, this parameter 

is not available in the equipment configuration menu.

 

4.5.- 

Measurement in 2 or 4 quadrants (power 

consumption and/or generation).

 

On screen the words “

SET QuAd

” appear  

(

2

=Power consumption / 

4

=consumption and 

generation)

 

4.6.- Setting the Power demand meter: 

 a) Electrical parameter to control: ("

SET Pd Code

"): 

None 

 

00 

Three-phase active power 

kW III 

16 

Three-phase apparent power 

kVA III 

34 

Three-phase current 

AIII 

36 

Current per phase 

A1-A2-A3 

A-ph 

Integrated parameter value according to the set period. 

 b) Integration period (1….60 minutes): ("

Pd Per 15

") 

 c) Clear maximum value recordings of Pd: ("

CLr Pd 

no

”) “

no

” or “

YES

”. 

4.7.- Setting display or omitting screens 

This option allows the page display format to be 
displayed

 

("

dEF Page YES / no

”)

 

I.

YES

  | Standard: se all electrical parameters are 

displayed. 

II.

no

 | Custom: by using the “

YES

” or “

no

” option the 

pages to be displayed when the equipment is on 

are selected. 

4.8.- Setting the start screen 

This option allows select the screen and selection 
mode of display screens (“

SET iniT page

”)

 

I.

Fixed page

: selects which page from the possible 

pages will appear first when applying voltage (or 

on RESETTING) to the  

CVM-MINI

 

-Ethernet

 . 

II.

Rotating pages

: selecting rotating pages (when all 

of the electrical parameters flash), automatically 

rotates, every 5 seconds it moves on to the 

following screen. 

 
 
 
 
 