MI 2883 Energy Master
Introduction
11
DPF
ind/cap
Recorded phase displacement (fundamental) power
factor or cos
, including
DPFp
ind/cap
(phase p power
displacement).
Minus sign indicates generated
power and plus sign indicates
consumed
power.
Suffix
ind/cap
represents inductive/
capacitive
character.
This
parameter
is
recorded
separately for each quadrant
as shown on figure. See 5.1.5
for definition.
DPF
+
totind
DPF
+
totcap
Instantaneous positive sequence fundamental power
factor.
Minus sign indicates generated power and plus sign
indicates consumed power. Suffix
ind/cap
represents
inductive/capacitive character. See 5.1.5 for definition.
DPF
+
totind
DPF
+
totcap
Recorded
total
effective
fundamental power factor.
Minus sign indicates generated
power and plus sign indicates
consumed power. Suffix
ind/cap
represents inductive/capacitive
character. This parameter is
recorded separately as shown
on
figure.
See
for
definition.
Dı
Phase current distortion power, including
Dı
p
(phase p
current distortion power). See 5.1.5 section: Power
measurement (Standard compliance: IEEE 1459-2010)
for definition.
Deı
tot
Total effective current distortion power. See 5.1.5 section:
Power measurement (Standard compliance: IEEE 1459-
2010) for definition.
D
H
Phase harmonics distortion power, including
D
H
p
(phase
p harmonics distortion power). See 5.1.5 section: Power
measurement (Standard compliance: IEEE 1459-2010)
for definition.
De
H
Total effective harmonics distortion power. See 5.1.5
section: Total nonfundamental power measurements for
definition.
Dᴠ
Phase voltage distortion power, including
Dᴠ
p
(phase p
voltage distortion power). See 5.1.5 section: Power
measurement (Standard compliance: IEEE 1459-2010)
for definition.
Deᴠ
tot
Total effective voltage distortion power. See 5.1.5
270
0
DPF
ind+
Le
ad
L
a
g
DPF
cap+
DPF
cap-
DPF
ind-
180
0
90
0
0
0
+P
-P
-Q
+Q
I
II
III
IV
270
0
Le
ad
L
a
g
180
0
90
0
0
0
+P
-P
-Q
+Q
I
II
III
IV
DPF
+
DPF
+
DPF
+
totcap-
DPF
+
totind-