MI 2883 Energy Master
Introduction
14
indicates positive sequence of consumed power.
See 5.1.5 for definitions.
P
H
Instantaneous phase active harmonic power, including
P
Hp
(phase p active harmonic power). Minus sign
indicates generated and plus sign indicates consumed
power. See 5.1.5 for definitions.
P
H
Recorded phase active harmonics power, including
P
Hp
(phase p active harmonic power). Minus sign indicates
generated and plus sign indicates consumed power. See
5.1.5 for definitions.
P
Htot
Instantaneous total active harmonic power. Minus sign
indicates generated and plus sign indicates consumed
power. See 5.1.5 for definitions.
P
Htot
Recorded total active harmonics power. Minus sign
indicates generated and plus sign indicates consumed
active power. See 5.1.5 for definitions.
PF
ind
PF
cap
Instantaneous phase combined
(fundamental
and
nonfundamental) power factor,
including
PF
p
ind/cap
(phase p
power
factor).
Minus
sign
indicates generated power and
plus sign indicates consumed
power.
Suffix
ind/cap
represents inductive/capacitive
character.
Note: PF
= DPF when harmonics are not present. See
5.1.5 for definition.
PF
ind
PF
cap
Recorded phase combined
(fundamental
and
nonfundamental) power factor.
Minus sign indicates generated
power and plus sign indicates
consumed
power.
Suffix
ind/cap
represents inductive/
capacitive
character.
This
parameter is recorded separately for each quadrant as
shown on figure.
PFe
totind
PFe
totcap
Instantaneous total effective combined (fundamental and
nonfundamental) power factor.
Minus sign indicates generated power and plus sign
indicates consumed power. Suffix
ind/cap
represents
inductive/capacitive character. See 5.1.5 for definition.
PFe
totind
Recorded total effective combined (fundamental and
nonfundamental) power factor.
270
0
+PF
ind
Le
ad
L
a
g
+PF
cap
-PF
cap
-PF
ind
180
0
90
0
0
0
+P
-P
-Q
+Q
I
II
III
IV
270
0
PF
ind
+
Le
ad
L
a
g
PF
cap
+
PF
cap
-
PF
ind
-
180
0
90
0
0
0
+P
-P
-Q
+Q
I
II
III
IV