MI 2883 Energy Master
Technical specifications
158
Active harmonic
power* (W)
Ph
1
, Ph
2
, Ph
3
, Ph
tot
0.000 k ÷ 999.9 M
4 digits
Excluding clamps
(Instrument only)
Ph > 1%
P
±1.0%
Ph
Current distortion
power* (var)
D
I1
, D
I2
, D
I3
, De
I
,
0.000 k ÷ 999.9 M
4 digits
Excluding clamps
(Instrument only)
D
I
> 1%
S
±2.0 %
D
I
Voltage distortion
power* (var)
D
V1
, D
V2
, D
V3
, De
V
0.000 k ÷ 999.9 M
4 digits
Excluding clamps
(Instrument only)
D
V
> 1%
S
±2.0 %
D
V
Harmonics distortion
power* (var)
D
H1
, D
H2
, D
H3
,De
H
0.000 k ÷ 999.9 M
4 digits
Excluding clamps
(Instrument only)
D
H
> 1%
S
±2.0 %
D
H
Apparent
nonfundamental
power* (VA)
S
N1
, S
N2
, S
N3
,Se
N
0.000 k ÷ 999.9 M
4 digits
Excluding clamps
(Instrument only)
S
N
> 1%
S
±1.0 %
S
N
Apparent harmonic
power* (VA)
S
H1
, S
H2
, S
H3
,Se
H
0.000 k ÷ 999.9 M
4 digits
Excluding clamps
(Instrument only)
S
H
> 1%
S
±2.0%
S
H
*Accuracy values are valid if I
10 % I
Nom
and U
80 % U
Nom
6.2.10
Power factor (PF)
Measuring range
Resolution
Accuracy
-
1.00 ÷ 1.00
0.01
± 0.02
6.2.11
Displacement factor (DPF) or Cos
φ)
Measuring range
Resolution
Accuracy
-
1.00 ÷ 1.00
0.01
± 0.02