Technical Manual
–
Central Operation Unit Smart
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
93
93
Shift value
Two-button function
With the function "send values - shift values", values can be moved up or down within the set limits.
The following figure shows the available settings:
Figure 52: Settings "send values" - shift values
The following table shows all available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Datapoint type
▪
1 Byte (0...100%)
▪
1 Byte (0…255)
Sets the datapoint type for the
value shift
Lower limit
0 - 100% / 0 - 255
[0 / 0]
Sets the lower limit value for
the value shift
Upper limit
0 - 100% / 0 - 255
[100% / 255]
Sets the upper limit value for
the value shift
Step width
0 - 100% / 0 - 255
[10% / 10]
Sets the step width between
two sending commands
Repeated sending at pressed
key
▪
Inactive
▪
active
Activation of the sending
repetition while pressing the
button
Repetition time
200 ms
–
3 s
[1 s]
Repetition time between two
telegrams while pressing the
button
Switching considers status
object
•
Yes
•
No
Setting whether the value
should be moved according to
the current status
Table 87: Settings "send values" - shift values