4.8 Temperature/Ventilation
4.8.1 Temperature measurement
The following picture shows the menu for temperature measurement:
Figure 18: Settings - Temperature measurement
The table shows the possible parameterization options for this setting range:
ETS-Text
Dynamic range
[Default value]
Comment
Send measurement value at
change
not send
0,1 K - 2,0 K
Sending condition for the measured
value
Send measurement value
cyclic
not send
1 min
–
60 min
Cyclic sending of the measured value
Send min/max value
▪
not send
▪
send
Sending condition for min/max values
Internal sensor correction
value (value *0,1 K)
-50
–
50
[0]
Temperature adjustment for internal
sensor
Internal/External sensor
▪
100% internal
▪
90% internal/ 10% external
▪
80 % internal/ 20% external
▪
…
▪
100% external
Setting the weighting between internal
and external sensor
Messages
▪
inactive
▪
active
Activation of the message function
Message if temperatur >
18 °C
–
40 °C
[26 °C]
Setting range of the upper signal value.
Only visible when
Messages
are active
Message if temperatur <
1 °C
–
25 °C
[13 °C]
Setting range of the lower signal value.
Only visible when
Messages
are active
Table 28: Settings - Temperature measurement