Technical Manual
–
Central Operation Unit Smart
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Phone: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
18
18
103
Push Buttons 1/2
State of shutter for display
State of blind for display
1 Byte
Low
X
X X X
103
Push Buttons 1/2
State basis comfort setpoint
2 Byte
Low
X
X X X
103
Push Buttons 1/2
State setpoint shift
1 Byte/
2 Byte
Low
X
X X X
104
Push Button 1
Push Buttons 1/2
Blocking object
1 Bit
Low
X
X X X
+5
next Button
Table 8: Communication objects
–
Direct buttons
Standard settings general objects
No.
Name
Function
Length
Priority
C R W T U
120
Operation
Output
1 Bit
Low
X X
X
121
Day/Night
Day = 1 / Night = 0
Day = 0 / Night = 1
1 Bit
Low
X
X X X
122
Presence
Input
1 Bit
Low
X
X X X
123
Buttons activation
Output
1 Bit
Low
X X
X
124
Display
Brightness
1 Byte
Low
X
X
125
Time
Receive/Send current value
3 Byte
Low
X
X X X
126
Date
Receive/Send current value
3 Byte
Low
X
X X X
127
Time / Date
Receive/Send current value
8 Byte
Low
X
X X X
135
–
138
Message 1-4
(Message 1 highest
priority)
Input
1 Bit
Low
X
X X X
139
Message text
(lowest priority)
Input
14 Byte
Low
X
X X X
140
141
State text 1
State text 2
Input
14 Byte
Low
X
X X X
142
–
144
State value 1-3
Input
1 Bit
1 Byte
2 Byte
Low
X
X X X
Table 9: Communication objects
–
General objects
The preset default settings can be taken from the tables above. The priority of the individual
communication objects as well as the flags can be adapted as required by the user. The flags assign
the respective task to the communication objects in the programming. C stands for communication,
R for reading, W for writing, T for transmission, and U for updating.