96
41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
19.4.8
In the Navigation Bar, click on Communication(s), expand the 98-Modbus Master item,
and then double-click on Entry#1.
19.4.9
Set Master Comm. to Enable.
19.4.10
Set Comm. Type to Read.
19.4.11
Set the Address to the Modbus address of the HMA.
19.4.12
Set the Start Register to 1302 (the start of the PV register for Slave 1 in the HMA).
19.4.13
Set the Num Entries to 4 (four 32-bit floating point numbers).
19.4.14
The Host IP Address, Host Port Number, AutoMitter Mode, Extended Addressing and
Encap Modbus Format can be ignored.
19.4.15
Set the Modbus Function Code to FC04 - Read Input Register.
19.4.16
Set the Flt Pt Register Size to 2 * 16-Bit register, and the FP Byte Order to Daniel (4,3,2,1).
19.4.17
Set the 16-Bit Register to Disabled.
19.4.18
Click on Apply to send the settings to the AutoPILOT PRO.