84
41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
18.3.7
Select View \ Advanced from the PCCU32 menu bar.
18.3.8
Click on Communications in the tree-view window.
18.3.9
Click on the Port name associated with Modbus RTU.
18.3.10
Select ‘Tank Gauge’ for the Protocol.
18.3.11
Set the Unkey delay to 3 ms.
18.3.12
Ensure that the communications settings match the settings of the HMA performed in
step 18.1.1. For example,
18.3.13
Click on ‘Send changes to device’
after all settings are changed and verified.