41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
11
1.4.5
Verify that the values in the registers listed in the Mbpoll window match the values for the
desired Modbus protocol settings. Refer to Appendix F for the HMA Communication
settings. If the settings do not match, double-click on a value that needs to be changed in
order to open the Write Single Register dialog, enter the new value, and then click on
Send.
1.4.6
Change DIP switch 1 to ON. This sets the device to run in the selected communications
mode.
1.4.7
If communication at the new settings is not achieved, change DIP switch 1 to OFF. This
sets the device to run in the default Modbus RTU communications mode. Check the
communication setting registers to ensure that the desired values are present.