41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
45
13.4.28
Open or click on an Mbpoll window, select Setup\Read\Write Definition from the menu
bar, ensure that the settings are as follows (the Slave ID should match the address
entered into register 3001 in step 13.4.1), and then click OK:
13.4.29
Verify that the Tx count in the Mbpoll window is increasing, the Err count is not increasing
and there are no reported communication errors.
13.4.30
Verify that register 3008 is set to 0.
13.4.31
If unable to establish communication in the HART over RS-485 mode, the HMA can be
reset to normal Modbus operating mode by switching DIP switch 1 to OFF. The HMA will
switch into the default communication mode. Using Procedure 1, set register 3008 to 0.
The HMA can be used either in that mode, or by setting DIP switch 1 to ON it can be used
in its normal Modbus configuration mode.