100
41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
In the Navigation Bar, click on Communication(s), expand the 98-Modbus Master item, and then
double-click on Entry#1.
19.5.8
Set Master Comm. to Enable.
19.5.9
Set Comm. Type to Write.
19.5.10
Set the Address to the Modbus address of the HMA.
19.5.11
Set the Start Register to 3100 (the start of the Blocking Distance register for Slave 1 in the
HMA).
19.5.12
Set the Num Entries to 1 (one 32-bit floating point number).
19.5.13
The Host IP Address, Host Port Number, AutoMitter Mode, Extended Addressing and
Encap Modbus Format can be ignored.
19.5.14
Set the Modbus Function Code to FC03/FC16 R/W Multiple for reading input registers.
19.5.15
Set the Flt Pt Register Size to 2 * 16-Bit Registers, and the FP Byte Order to Daniel
(4,3,2,1).
19.5.16
Set the 16-Bit Register to Disabled.
19.5.17
Click on Apply to send the settings to the AutoPILOT PRO.