90
41-621.1 HART
®
to Modbus
®
Adaptor Operating Manual
18.4.15
To display the values,
18.4.16
Select Communications \ LevelMaster \ Tank Calibrate \ Tank x from the tree-view
window of the PCCU32.
18.4.17
Set the number of Tank Sections in row 51.108.x.
18.4.18
For each tank section, set the height of that section in rows 51.109.x
18.4.19
For each tank section, enter the Factor in rows 51.110.x. The Factor value is the number
of barrels per ¼ inch of height in that section. By clicking on the Help button of the
PCCU32 and searching for ‘tank calibration’, a more detailed explanation of the calibration
process can be obtained.