TR30-G USERS MANUAL EM-8631-G Rev.16
Basic setting (PI)
Once the assignment is complete, please configure the following basic setting. Click on the [OK] button to
temporarily store the setting.
Parameter
Description
CH name
Set a channel name which is less than 16 characters.
CH comment
Set a description for the channel which is less than 16 characters using the tag name,
etc.
Scaling
Set the weight per pulse as a numeric value.
Number of decimal places
Set the number of digits after the decimal point in the values displayed as numeric
values in the Web screen.
You can set a value between 0 and 3.
Engineering unit
Set the engineering unit corresponding to the actual value set in the [Scale].
Can be set as less than 8 characters.
Filter
Set by selecting from: None/Moving average/Delay buffer.
Can only be set for actual values
Analog accumulation
• Accumulation rate
Set the equivalent number of pulses (0 to 10000), in the case of target AI is entered as
100% and this continues for unit time.
•Time Unit
Set minute/hour/day.
• Low-end cut out
Set the lower limit values(0 to 12000) per one sampling.
Reset input
The cumulative total pulse can be reset on the rising edge of the Discrete input (DI). If
this function is not being used, set it as [Disable], and if it is being used, set the target
DI.
Exponent notation
Choose to use the normalized exponent notation for numeric values on the web brows-
er views. The number of decimal places set in the above is also used in the mantissa.
PI setting