![background image](http://html.mh-extra.com/html/m-system/tr30/tr30_user-manual_683658065.webp)
65
TR30-G USERS MANUAL EM-8631-G Rev.16
Parameter
Description
CH name
Set a channel name which is less than 16 characters.
CH comment
Set a description for the channel which is less than 16 characters using the tag name, etc.
Invert logic
If the ON/OFF in the input signal and the ON/OFF in the application signal are the reverse of each
other, put a check in the check box.
Status
(ON)
(OFF)
• Display comment
Set strings corresponding to ON/OFF respectively. Can be set as less than 8 characters.
• Color
Set the colors which represent the status displayed on the Web screen for ON/OFF respectively.
• Event log
Set whether or not to record the event summary from the Web screen when there is a change in
the input values. To record, put a check in the check box.
• Acknowledge
You can set whether Acknowledge is required for ON/OFF respectively.
• Register new event
Set whether or not to display as a new event when there is a change in the input values and it
enters a certain zone. To display, put a check in the check box.
• On delay time/Off delay time
Set the number of samples for the delay time for ON/OFF respectively.
(Setting range: 0 to 999)
For example, with a sampling cycle of 100 msec., if the [On delay time] is set as 10, the unit is rec-
ognized as being ON when the input signal has been continuously ON for 1 second (1000 msec.).
And, if the sampling cycle is changed to 1 second in this state, the delay time becomes 1 second
× 10 which is 10 seconds, and the unit is then recognized as being ON when the input signal has
been continuously ON for 10 seconds.
➔
7.3.3 Storing rate and sampling cycle
• Event number
The event number can be set for ON/OFF respectively. This number can be used to set a filter in
the event summary in the Web screen. (Setting range: 1 to 32)
• Message
Set a message which is less than 32 characters to be displayed for each event.
• E-mail
Set the mail number to be sent when an event occurs.
➔
• Trigger recording
Set whether or not to record when there is a change in the input value and the status changes.
You can select from: Disable / Start / Stop.
• New memory block
Set when or not to run a new memory block when there is a change in the input value and the
status changes. You can select from: Disable / Enable.