(3) Set the [CH setting] as [SLMP], and enter the parameters in the table below.
1. Select
2. Enter
3. Enter
Parameter
Description
Slave No.
Enter the slave No. (0 to 11) set in (1).
SLMP device
Choose the device code of the SLMP device to be connected.
SLMP device No.
Set the device No. of the SLMP device to be connected.
When the slave type of the selected Slave No. is [SLMP 16bit], set the device
No. of the smaller number because the PI data is 32 bit data set in two ad-
dresses.
Check or uncheck the [Invert] check box depending on the order of high/low
devices.
Measuring mode
(Modbus/TCP·SLMP)
Set the type of the 32 bit data read from the remote I/O.
Select from the following.
• Accumulation
The cumulative total is calculated by accumulating the difference between the
value at the start of cumulative totalizing and the value when it is reset, for each
sampling duration. This corresponds to the cumulative total data of the SLMP
device.
• Actual value
The retrieved data is recognized as a signed 32 bit integer, and its value is taken
as sampling data. This corresponds to the power data of the SLMP device.
• Float
The retrieved data is recognized as single precision floating point, and its value
is taken as sampling data. This corresponds to the power data of the SLMP
device.
Pulse range
Set the same value as the pulse range set in the SLMP device.
For details, please see the User Manual for the SLMP device which you are us-
ing.