30
TR30-G USERS MANUAL EM-8631-G Rev.16
3.7 SLMP device connection setting
Using the SLMP client function of the TR30, I/O can be expanded using SLMP devices.
At the maximum of 12 SLMP devices can be connected to single TR30 device. Please set different IP ad-
dresses which do not overlap with the address of the TR30 for the SLMP device (Slave 0 to Slave 11).
■
SLMP-compatible devices that can be connected to the TR30
• MELSEC iQ-R Series (Mitsubishi Electric)
• MELSEC iQ-F Series (Mitsubishi Electric)
• MELSEC Q Series (Mitsubishi Electric)
■
Tested and verified SLMP-compatible CPU modules
•
R04CPU
•
FX5U-32M
•
Q03UDECPU
■
Connecting CPU modules for SLMP
The TR30 is connected to SLMP devices by TCP/IP over the Ethernet.
In order that the TR30 communicates with an SLMP device, register the device on Ethernet Configuration set-
ting window and set as follows:
Communication data code: Binary
Communication method: SLMP
Protocol: TCP
IP address: IP address specified in the I/O slave setting of the TRGCFG
Port No.: Port No. specified in the I/O slave setting of the TRGCFG
NOTES
• Please refer to the Users Manual of each product for the SLMP setting.
• When connecting to the TR30 via WAN, it is strongly recommended to use VPN in terms of
security.
Switching HUB
Slave 0
TR30
MELSEC iQ-R
Series
CPU Module
Slave 1
MELSEC iQ-F
Series
CPU Module
Slave 2
MELSEC Q
Series
CPU Module