For types 48 (door contact), 50 (light), 54 ( surge protection) and 55 (vandalism) the
value (after value mapping if appropriate) can be inverted (see uplink configuration
above). For Types 48, 54 and 55, the default is to invert the value, e.g. a value of “0”
is reported as “door open”, “surge protection defect” or “vandalism alarm”
respectively, and a value “not 0” is reported as “door closed”, “surge protection ok” or
“no vandalism alarm”.
For types 51, 52 and 53, an appropriate value mapping must be configured and
assigned to the sensor channel.
For type 51, a pre-
defined “default” value mapping is applied if there is no value
mapping assigned to the sensor channel
6.1.3.2 Manufacturer defined data types FG6
6.1.3.2.1 Type 151
– status power supply
Position
Description
Value
Byte 1
Length
Length of the de block
Byte 2
Channel
[1..254 ]
Byte 3
DE-Type
[ 151 ]
Byte 4
Supplier-code
47 (Lufft)
Byte 5
See table
BIT
STATUS 0
STATUS 1
0
Power ok (BM=open)
Power failure (BM=closed)
1
UPS ok (BA=open)
UPS defect (BA=closed)
2
n/a
n/a
3
n/a
n/a
4
GFCI (FI) ok
GFCI (FI) fired
5
Circuit breaker (SI) ok
Circuit breaker (SI) off