Mounting the heat baffle
.................................................................................................................................................................................................................................
Purpose
The heat baffle is necessary to lead the heated air out of the rack.
Mounting
Proceed as follows to mount the heat baffle:
.................................................................................................................................................................................................
1
Place the heat baffle (DC1006077, item 1) directly above the mounted
LambdaUnite
®
MSS subrack at the rack rear side as shown in the figure below. Be sure to have the
correct direction.
.................................................................................................................................................................................................
2
Mount the heat baffle at hole positions #24 and #27 (see section
using M6x16 screws (CC901331421).
NOTE:
The hole numbering is counted from top to bottom of the rack frame.
E
N D
O F
S
T E P S
........................................................................................................................................................................................................................
Figure E-3 Mounting the heat baffle
Mixed configuration:
LambdaUnite
®
MSS and
Metropolis
®
DMX (High Capacity)
.................................................................................................................................................................................................................................
365-374-187
Issue 1, December 2005
Lucent Technologies - Proprietary
See notice on first page
E-5