Complete the following steps to mount an ETSI-2 rack on the floor:
.................................................................................................................................................................................................
1
Drill the necessary holes (18 mm [0.7”] in diameter and 100 mm [4”] in depth) in the
floor (*1).
.................................................................................................................................................................................................
2
Put the rack frame in place.
.................................................................................................................................................................................................
3
Put the anchor (CC408414951, item 2) through the anchor hole provided in the rack
bottom plate.
.................................................................................................................................................................................................
4
Balance the rack frame in a horizontal position using the adjustable feet
(CC407890623, item 3).
Important!
25 mm [1”] should be between the floor and the rack before levelling
the rack. This initial adjustment of the feet ensures that it is still possible to level
the next rack.
.................................................................................................................................................................................................
5
Push or tap the anchor until the plate washer is flat against the rack frame.
.................................................................................................................................................................................................
6
Tighten the bottom plate of the rack (item 1) to the floor using the nut of the anchor.
.................................................................................................................................................................................................
7
Place the safety/dust cap over the nut.
Mechanical installation
Floor mounting
.................................................................................................................................................................................................................................
3-10
Lucent Technologies - Proprietary
See notice on first page
365-374-187
Issue 1, December 2005