LTC3882-1
25
Rev A
OPERATION
or for PWM control protocol 0, reverse overcurrent is
detected. See I
OUT
faults below.
UV faults and warnings are masked if the channel has
been commanded off or until all of the following criteria
are achieved.
• TON_DELAY Has Expired
• TON_RISE Ramp Has Completed
• TON_MAX_FAULT_LIMIT Has Been Reached
• IOUT_OC_FAULT_LIMIT Has Not Been Reached
• TOFF_FALL Is Not in Progress
Output UV warnings are determined from multiplexed
monitor ADC conversions. The LTC3882-1 has no hard-
wired PWM response for output UV faults or warnings.
Power Good Indication (Master)
An LTC3882-1 master phase indicates Power Good on its
PGOOD pin and in PMBus commands STATUS_WORD
(paged) and MFR_PADS_LTC3882-1 based on pro-
grammed UV and OV fault limits. Power Good is indicated
on a master phase as long as it is enabled to run and V
OUT
is between the UV and OV fault limits. If a master chan-
nel is off for any reason, its PGOOD pin is driven low and
Power Not Good is indicated in the status commands.
Power Good Indication (Slave)
As long as they are enabled, slave phases indicate Power
Good on PGOOD and in PMBus status commands, unless
a master error amplifier (EA) fault is detected. An EA fault
indicates the bussed COMP voltage appears to be too high.
When a slave detects an EA fault, its output is immedi-
dately disabled and OV is indicated (see Figure 2). Any
valid higher-level OV fault response and propagation may
be set for a slave channel to handle a detected EA fault. If
the OV fault response is set to ignore, the slave output is
re-enabled when the EA/COMP condition clears.
A slave indicates Power Not Good with PMBus status com-
mands during an EA fault, but its PGOOD pin remains high
impedance. If a slave phase is off for any other reason, its
PGOOD pin is also driven low.
Hardwired PWM Response to I
OUT
Faults
The LTC3882-1 measures average I
OUT
from the voltage
across the I
SENSE
pins, taking into account the sense resistor
or DCR value and its associated temperature coefficient.
Both are provided by PMBus command or EEPROM values.
An output overcurrent (OC) fault condition is detected by
a supervisor comparator for each PWM output when the
sensed instantaneous current for that channel reaches
its maximum allowed value. Refer to the IOUT_OC_
FAULT_LIMIT PMBus command for details. When an OC
fault is detected the controller immediately disables the
top FET, and the bottom FET is normally commanded on
for the remainder of that PWM cycle.
If programmed to operate in CCM, the LTC3882-1 also
uses the negative of IOUT_OC_FAULT_LIMIT to detect
a reverse overcurrent (ROC) fault. When an ROC fault
occurs the controller immediately disables both top and
bottom FETs, unless PWM output protocol 1 is selected
with MFR_PWM_MODE_LTC3882-1.
OC and ROC faults are both handled according to the
IOUT_OC_FAULT_RESPONSE for that channel. Either
hardware response can result in current-limited operation
using pulse truncation or skipping. Because the LTC3882-1
uses leading edge modulation, this will cause a shift in
average phase toward 0° on the faulted channel and an
increase in input ripple current
Output OC warnings are determined from multiplexed
monitor ADC conversions. The LTC3882-1 has no hardwired
PWM response if an output OC warning occurs.
Hardwired PWM Response to Temperature Faults
An internal temperature sensor measured by the moni-
tor ADC protects against EEPROM and other IC damage.
When die temperature rises above 130°C, the LTC3882-1
will NACK any EEPROM-related command except RE-
STORE_USER_ALL and MFR_RESET and issue a CML
fault for Invalid/Unsupported Command. Normal EEPROM
access is re-enabled when die temperature drops below
125°C. Above 160°C, the part shuts down all PWM outputs
until die temperature is below 150°C. Internal temperature
fault limits cannot be adjusted. Writing to the EEPROM
above a die temperature of 85°C is strongly discouraged.